Power circuit breaker x160 4P 40kA 100A HNA101H

local index:
ALI079HAGE
Catalog No:
HNA101H
EAN code:
3250613130985
Manufacturer: HAGER
Rated frequency [Hz]: 50/60
Number of poles: 4
Rated insulation voltage [V]: 690
Price:
592,29 €
gross / pcs.
(including VAT 23%)
Delivery in 3h
up to 10 weeks (business days)
Pickup in 1h
Quantity pcs.
(multiplicity:
1
)
Add to clipboard
Print

Product description

All power circuit breakers, power disconnectors, power switches and residual current blocks have one common feature - they are perfectly adapted to meet the current requirements resulting from everyday electrical installation practice. Various connection options and a wide range of equipment allow for the implementation without much effort, even unusual solutions on the implemented facilities.

Size x160:
Power switches:
• equipped with thermal-magnetic triggers
• thermal element adjustment in the range from 0.63 to 1xIN
• permanent magnetic term 10xIN
• compliant with IEC 60947-2
Power switches:
• for switching on and off operating currents, not equipped with triggers
• accessories as for switches
• Icw (1s) = 2 kA
• compliant with IEC 60947-3, cat. AC22/23A

Features:
• mounting on TS35 rail or mounting plate
• cage clamps for connecting copper wires as standard
• cage clamps for aluminum conductors available as accessories
• equipped with connector measuring tips
• TEST mechanical button
• integrated lever lock under the padlock max. 4 mm
• cage clamps:
- wire from 6 to 95 mm²
- line from 6 to 70 mm²

Technical data

  • Rated frequency [Hz]
    50/60
  • Rated insulation voltage [V]
    690
  • Surge voltage [V]
    8000
  • power loss [W]
    35.7
  • Mechanical durability (number of cycles)
    4000
  • Number of modules
    6
  • Number of poles
    4
  • Connection
    With a screw
  • Rated current [A]
    100
  • Electrical endurance (number of cycles)
    1000
  • Rated switching voltage [V]
    220/415
  • PKWIU
    27.12.22.0

Other technical data

  • Rated permanent current Iu
    100 A
  • Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
    40 kA
  • Adjustment range undelayed short-circuit release
    1500 ... 1500 A
  • Type of electrical connection of main circuit
    Screw connection
  • Suitable for DIN rail (top hat rail) mounting
    Yes
  • Number of auxiliary contacts as normally closed contact
    0
  • Number of auxiliary contacts as change-over contact
    0
  • Number of poles
    4
  • Type of control element
    Toggle
  • Motor drive integrated
    No
  • Degree of protection (IP)
    IP40
  • Rated voltage
    220 ... 415 V
  • Overload release current setting
    63 ... 100 A
  • Integrated earth fault protection
    No
  • Device construction
    Built-in device fixed built-in technique
  • DIN rail (top hat rail) mounting optional
    No
  • Number of auxiliary contacts as normally open contact
    0
  • With switched-off indicator
    Yes
  • Position of connection for main current circuit
    Front side
  • Complete device with protection unit
    Yes
  • Motor drive optional
    No

Bulk packaging

A kind of package Karton Pakiet Paleta
Quantity 1 pcs. 1 pcs. 6 pcs. 144 pcs.
Weight (kg) 1,200 1,324 8,310 222,440
Width (m) 0,100 0,148 0,315 0,800
Length (m) 0,096 0,117 0,212 0,998
Depth (m) 0,130 0,168 0,362 1,200