Technical data

  • Characteristic
    b
  • Depth [mm]
    70
  • Tightening torque [Nm]
    3.5 to 5
  • Rated current [A]
    125
  • Power dissipation [W]
    20
  • Power loss per pole [W]
    9.93
  • Connection type
    Clamps with alignment system
  • Electrical endurance (number of cycles)
    4000
  • Operating temperature range [°C]
    from -5 to 60
  • Rated short-circuit breaking capacity Icn [kA]
    15
  • Max/min value of the AC current of the protection activation
    3/5 In
  • Ultimate short-circuit breaking capacity Icu for 240V [kA]
    15
  • Ultimate short-circuit breaking capacity Icu for 415V [kA]
    15
  • Rated current at 30°C [A]
    125
  • Rated current at 45°C [A]
    115.7
  • Rated current at 55°C [A]
    109.1
  • Service short-circuit breaking capacity Ics [%]
    50
  • storage temperature [°C]
    from -25 to 80
  • Rated current correction factor for 2 devices installed side by side
    1
  • Rated surge voltage [V]
    6000
  • Wire cross-section (cord) [mm²]
    35
  • PKWIU
    27.12.22.0
  • Rated frequency [Hz]
    60
  • Number of poles
    1
  • Rated insulation voltage [V]
    500
  • Level of security
    IP20
  • power loss [W]
    9.93
  • Width [mm]
    27
  • Height [mm]
    90
  • Mechanical durability (number of cycles)
    20000
  • Rated switching voltage [V]
    240/415
  • Number of modules
    1.5
  • Ultimate short-circuit breaking capacity Icu for 230V [kA]
    15
  • Ultimate short-circuit breaking capacity Icu for 400V [kA]
    15
  • Ultimate short-circuit breaking capacity per pole for 400V [kA]
    4.5
  • Rated current at 40°C [A]
    119
  • Rated current at 50°C [A]
    112
  • Rated current at 60°C [A]
    105.6
  • Operating short-circuit breaking current Ics [kA]
    7.5
  • Supply voltage type
    AC
  • Rated current correction factor for 3 devices installed side by side
    0.95
  • Number of protected poles
    1
  • Conductor cross-section (wire) [mm²]
    70

Other technical data

  • Built-in depth
    70 mm
  • Number of poles (total)
    1
  • Rated current
    125 A
  • Rated insulation voltage Ui
    500 V
  • Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V
    15 kA
  • Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V
    15 kA
  • Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V
    15 kA
  • Concurrently switching neutral conductor
    No
  • Pollution degree
    3
  • Width in number of modular spacings
    1.5
  • Ambient temperature during operating
    -25 ... 70 °C
  • Connectable conductor cross section solid-core
    1 ... 70 mm²
  • Release characteristic
    B
  • Number of protected poles
    1
  • Rated voltage
    415 V
  • Rated impulse withstand voltage Uimp
    6 kV
  • Voltage type
    AC
  • Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V
    15 kA
  • Frequency
    50 ... 60 Hz
  • Over voltage category
    3
  • Additional equipment possible
    Yes
  • Degree of protection (IP)
    IP20
  • Connectable conductor cross section multi-wired
    1 ... 50 mm²

Bulk packaging

A kind of package Karton Pakiet Paleta
Quantity 1 pcs. 1 pcs. 36 pcs. 864 pcs.
Weight (kg) 0,239 0,240 9,005 239,120
Width (m) 0,026 0,080 0,310 0,800
Length (m) 0,090 0,040 0,130 1,010
Depth (m) 0,072 0,100 0,365 1,200