YKY 4x10 copper ground wire 0.6/1kV 112271055D0500

local index:
KEC268NKTQ
Catalog No:
112271055D0500
EAN code:
5907802032725
Manufacturer: NKT
Number of veins: 4
Color: Gray
Vein material: Copper
Large-size product
Price:
5,77 €
gross / m.
(including VAT 23%)
Delivery in 3h
Accessible 3107 m.
Pickup in 1h
Quantity m.
(multiplicity:
1
)
It is not possible to add more of this product to the cart. Goods at a promotional price can only be purchased in the quantity available in stock.
Add to clipboard
Print

Product description

Cables intended for permanent installation, indoors and outdoors, directly in the ground and in concrete enclosures, resistant to UV radiation

Technical data

  • Number of veins
    4
  • Vein material
    Copper
  • Rated voltage [V]
    600/1000
  • Core
    Wire
  • Accurate color
    Gray
  • PKWIU
    27.32.13.0
  • Color
    Gray
  • Insulation voltage [kV]
    0.6/1
  • Core cross-section [mm²]
    10
  • Core diameter [mm2]
    10
  • Insulation material
    PVC

Other technical data

  • Conductor surface
    Bare
  • Conductor category
    Class 1 = solid
  • Number of cores
    4
  • Specification core insulation
    Other
  • Laminated sheath
    No
  • Żyła ochronna
    No
  • Outer semi-conducting layer
    No
  • Drain wire
    No
  • Number of pilot/reduced conductors
    0
  • Armouring
    No
  • Specification material outer sheath
    Other
  • Conductive coating
    No
  • Longitudinal water blocking screen
    No
  • Reaction-to-fire according to EN 13501-6: Smoke production
    None
  • Reaction-to-fire according to EN 13501-6: Acidity
    None
  • Halogen free according to EN IEC 60754-2
    No
  • Low smoke (according to EN 61034-2)
    No
  • Trwałość izolacji zgodnie z IEC 60331
    No
  • Circuit integrity
    No
  • Outer diameter approx.
    16.78 mm
  • Permitted cable outer temperature after assembling without vibration
    -35 ... 70 °C
  • Nominal voltage U
    1 kV
  • Nominal cross section conductor
    10 mm²
  • Shape of conductor
    Round
  • Material core insulation
    Polyvinyl chloride (PVC)
  • Core identification
    Colour
  • Fibre optic elements
    No
  • Inner semi-conducting layer
    No
  • Screen
    No
  • Lead sheath
    No
  • Concentric conductor
    None
  • Material outer sheath
    Polyvinyl chloride (PVC)
  • Colour outer sheath
    Black
  • Longitudinal water blocking conductors
    No
  • Reaction-to-fire according to EN 13501-6: Class
    Eca
  • Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    None
  • Halogen free according to EN 60754-1/2
    No
  • Flame retardant
    According to IEC/EN 60332-1-2
  • Low smoke according to EN IEC 61034-2
    No
  • Wytrzymałość (trwałość) izolacji
    No
  • Olejoodporny zgodnie z IEC 60811-404
    No
  • Max. conductor temperature
    70 °C
  • Nominal voltage U0
    0.6 kV

Dane CPR (Construction Products Regulation)

  • Numer notyfikowanego laboratorium badawczego CE:
    2652
  • Numer referencyjny DoP (DWU)
    DOP000032_PL_Rev.1
  • Oznaczenie produktu
    YKYżo 0.6/1 kV 4x10
  • Nazwa producenta:
    NKT S.A., ul. Gajowa 3, 43-254 Warszowice
  • Reakcja na ogień:
    Eca
  • Zharmonizowana specyfikacja techniczna (norma):
    EN 50575
  • Zastosowanie:
    Do przesyłu energii elektrycznej do zastosowania w obiektach objętych uregulowaniami odnośnie reakcji wyrobów budowlanych na oddziaływanie ognia.