Circuit breaker, 3-pole, 80A, 36kA plug, motor protection 112746

local index:
ALI190MOEL
Catalog No:
112746
EAN code:
4015081122868
Manufacturer: EATON
Number of poles: 3
Installation: Plug-in technology
Rated current [A]: 80
Price:
434,17 €
gross / pcs.
(including VAT 23%)
Delivery in 3h
up to 4 weeks (business days)
Pickup in 1h
Quantity pcs.
(multiplicity:
1
)
Add to clipboard
Print

Product description

Circuit breakers of the NZM..-M series with only four compact sizes are suitable for all applications and are suitable for the IEC market. Assembly is always flexible with modular functional groups. With thermomagnetic release to protect the motor. Notes: with phase loss sensitivity, trip class 10A, IEC/EN 60947-4-1, IEC/EN 60947-2 MCBs meet all requirements of utilization category AC-3.

Technical data

  • Number of poles
    3
  • Rated current [A]
    80
  • Switching capacity [kA]
    36
  • Installation
    Plug-in technology
  • Series
    engine protection

Other technical data

  • Overload release current setting
    63 ... 80 A
  • With thermal overload protection
    Yes
  • Switch off technique
    Thermomagnetic
  • Rated permanent current Iu
    80 A
  • Rated operation power at AC-3, 400 V
    45 kW
  • Type of control element
    Rocker lever
  • With integrated auxiliary switch
    No
  • Number of poles
    3
  • Degree of protection (IP)
    IP20
  • Width
    95 mm
  • Adjustment range undelayed short-circuit release
    640 ... 1120 A
  • Phase failure sensitive
    Yes
  • Rated operating voltage
    690 ... 690 V
  • Rated operation power at AC-3, 230 V
    22 kW
  • Type of electrical connection of main circuit
    Other
  • Device construction
    Built-in device plug-in technique
  • With integrated under voltage release
    No
  • Rated short-circuit breaking capacity lcu at 400 V, AC
    22.5 kA
  • Height
    201 mm
  • Depth
    90 mm

Bulk packaging

A kind of package Skrzynia
Quantity 1 pcs.
Weight (kg) 1,227
Volume (m3) 0,002
Width (m) 0,095
Length (m) 0,090
Depth (m) 0,201