Power cable YKXS 4x16 RE 0.6/1kV 112200015

Indeks lokalny:
KEC003NKTQ
Numer katalogowy:
112200015
Kod EAN:
8591462026889
Producent: NKT
Number of veins: 4
Color: Blue | Brown | Black | Gray
Rated voltage [V]: 600/1000
Produkt wielkogabarytowy
Cena:
60,21 zł
gross / mb.
(w tym VAT 23%)
Dostępne 20 mb.
Odbiór za 1h
Ilość mb.
(wielokrotność:
1
)
Dodaj do zapytania ofertowego
Dodaj do schowka
Drukuj

Opis produktu

Power cable voltage 0.6/1 kV from the manufacturer NKT S.A. The product catalog number is 112200015.  ;Power cable (K) with copper conductors in polyethylene insulation (XS) and PVC sheath (Y). Intended for supplying low-voltage receivers with electricity, used for permanent installation indoors, directly in the ground, in ducts cables, on constructions, in places with little exposure to mechanical damage.

  • RE - single-wire round conductors class 1.
  • 4-core: blue, brown, black, gray .

Dane techniczne

  • Number of veins
    4
  • Rated voltage [V]
    600/1000
  • Cable outer diameter [mm]
    19.7
  • Vein class
    1
  • Color
    Blue Brown Black Gray
  • Core cross-section [mm²]
    16
  • Insulation material
    Cross-linked polyethylene
  • PKWIU
    27.32.13.0

Pozostałe dane techniczne

  • Conductor material
    Copper
  • Nominal cross section conductor
    16 mm²
  • Conductor resistance at 20 °C
    1.15 Ω/km
  • Number of cores
    4
  • Specification core insulation
    Crosslinked polyethylene (XLPE)
  • Core identification
    Colour
  • Fibre optic elements
    No
  • Inner semi-conducting layer
    No
  • Screen
    No
  • Lead sheath
    No
  • Radial water blocking cable
    No
  • Concentric conductor
    None
  • Specification material outer sheath
    Other
  • Cable geometry
    Round
  • Longitudinal water blocking conductors
    No
  • Flame retardant according to IEC 60332-1-2
    Yes
  • Flame retardant according to IEC 60332-3-22 (Cat A)
    No
  • Flame retardant according to IEC 60332-3-24 (Cat C)
    No
  • Low smoke according to EN IEC 61034-2
    No
  • Halogen free according to EN IEC 60754-2
    No
  • Reaction-to-fire according to EN 13501-6: Class
    Eca
  • Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
    None
  • Circuit integrity according to IEC 60331-1
    None
  • Circuit integrity according to IEC 60331-3
    None
  • Circuit integrity according to EN 50200 annex E
    No
  • Outer diameter approx.
    18 mm
  • Weight
    812 kg/km
  • Permitted cable outer temperature during assembling/handling
    -5 ... 40 °C
  • Nominal voltage U0
    0.6 kV
  • UV resistant
    Yes
  • Suitable as installation cable
    No
  • Suitable as medium-voltage cable
    No
  • Certified as airport lighting cable
    No
  • Conductor surface
    Bare
  • Conductor category
    Class 1 = solid
  • Shape of conductor
    Round
  • Material core insulation
    Polyolefin
  • Core identification according to HD 308 S2
    Yes
  • Laminated sheath
    No
  • With protective conductor
    No
  • Outer semi-conducting layer
    No
  • Drain wire
    No
  • Armouring/reinforcement
    None
  • Number of pilot/reduced conductors
    0
  • Material outer sheath
    Polyvinyl chloride (PVC)
  • Colour outer sheath
    Black
  • Conductive coating
    No
  • Longitudinal water blocking screen
    No
  • Flame retardant according to IEC 60332-3-21 (Cat A F/R)
    No
  • Flame retardant according to IEC 60332-3-23 (Cat B)
    No
  • Flame retardant according to IEC 60332-3-25 (Cat D)
    No
  • Halogen free according to EN IEC 60754-1
    No
  • Halogen free according to EN IEC 60754-3
    No
  • Reaction-to-fire according to EN 13501-6: Smoke production
    None
  • Reaction-to-fire according to EN 13501-6: Acidity
    None
  • Circuit integrity according to IEC 60331-2
    None
  • Circuit integrity according to EN 50200
    None
  • Oil resistant according to EN IEC 60811-404
    No
  • Min. permitted bending radius, stationary application/permanent installation
    216 mm
  • Max. conductor temperature
    90 °C
  • Permitted cable outer temperature after assembling without vibration
    -35 ... 90 °C
  • Nominal voltage U
    1 kV
  • Suitable for underground installation
    Yes
  • Certified for shipboard application
    No
  • Suitable as high-voltage cable
    No
  • With rodent protection
    No

Dane CPR (Construction Products Regulation)

  • Numer notyfikowanego laboratorium badawczego CE:
    1014
  • Numer referencyjny DoP (DWU)
    DOP000081_PL, Revision 3
  • Oznaczenie produktu
    YKXS 4x16 RE
  • Nazwa producenta:
    NKT s.r.o. Kladno, ul. Průmyslová 1130, 272 01, Kladno
  • Reakcja na ogień:
    Eca
  • Zharmonizowana specyfikacja techniczna (norma):
    EN 50575
  • Zastosowanie:
    Do przesyłu energii elektrycznej do zastosowania w obiektach objętych uregulowaniami odnośnie reakcji wyrobów budowlanych na oddziaływanie ognia.

Dane producenta

  • Producent
    NKT s.r.o
  • Adres
    CZ 27201 Kladno Prumyslova 1130 Czechy
Zgłoś błąd