Motor contactor, Contactors up to 170 A, 3-pole,
AC-1: Non-inductive or weakly inductive loads, resistance furnaces,
AC-3: Motors squirrel cage motors: starting, shutdown during operation,
AC-4: Squirrel cage motors: starting, counter-current brakes, reversing mode, impulse mode,
Rated operational current AC-1 conventional thermal current , 3-pole, 50 - 60 Hz open at 40 °C: Ith =Ie= 45 A, enclosed: Ith= 36 A, Rated operational current AC-1 conventional thermal current 1-pole open: Ith= 100 A, in enclosure: Ith= 90 A, Max. rated power of three-phase motors 50 - 60 Hz AC-3 220 V 230 V: P= 11 kW, 380 V 400 V: P= 18.5 kW, 660 V 690 V: P= 21 kW rated power of three-phase motors 50 - 60 Hz AC-4 220 V 230 V: P= 4 kW, 380 V 400 V: P= 7 kW, 660 V 690 V: P= 10 kW, for combination with auxiliary switch module : DILA-XHI(V).., Contact arrangement R = NC contacts: 1 NO, Notes: Connection elements according to EN 50012., With mirror contact, Type of AC/DC current: AC operation
A kind of package | Skrzynia |
Quantity | 1 pcs. |
Weight (kg) | 0,447 |
Volume (m3) | 0,000 |
Width (m) | 0,047 |
Length (m) | 0,099 |
Depth (m) | 0,087 |