HA switch disconnectors from 125 to 3200 A. - Power switch for installation in univers N and univers N HC switchgears with components: - direct rotary drive, - In from 125 to 3200 A, - safe power on and off in low voltage circuits Additional equipment: - cage terminals (up to In = 630 A), - disconnector covers and terminal covers - auxiliary contacts, - rotary drive for mounting on the switchgear door.
Technical data
Number of poles
3
Level of security
IP20
PKWIU
27.12.22.0
Rated current [A]
250
Rated conditional short-circuit current [kA]
17
Other technical data
Version as main switch
Yes
Version as safety switch
Yes
Version as reversing switch
No
Max. rated operation voltage Ue AC
415 V
Rated permanent current Iu
250 A
Rated permanent current at AC-21, 400 V
250 A
Rated operation power at AC-23, 400 V
112 kW
Conditioned rated short-circuit current Iq
50 kA
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
0
Motor drive integrated
No
Device construction
Built-in device fixed built-in technique
Suitable for front mounting 4-hole
No
Suitable for distribution board installation
Yes
Colour control element
Black
Interlockable
Yes
Degree of protection (IP), front side
IP00
Version as maintenance-/service switch
Yes
Version as emergency stop installation
No
Number of switches
1
Rated operating voltage
380 ... 415 V
Rated permanent current at AC-23, 400 V
200 A
Rated short-time withstand current lcw
9 kA
Switching power at 400 V
164 kW
Number of poles
3
Number of auxiliary contacts as normally open contact