Isolating Load Switch. It is perfectly adapted to meet current requirements resulting from everyday electrical installation practice.
Current:
- Current carrying capacity of AC21 in category A: 3200 A ,
- Rated operational current (AC23), category A: 800 A,
- Current carrying capacity AC21 category B: 3200 A,
- Allowable current load AC22 Category A: 800 A,
- Allowable current load AC22 Category B: 800 A,
- Rated operational current (AC23), Category B: 800 A,
- Rated short-time withstand current Icw: 50 kA,
- Rated short-time withstand current 1s: 50 kA.
Power:
- Rated power below 660 V, 50 Hz: 185 kW,
- Active power below 380/415 V, 50 Hz: 450 kW,
- Rated switching power for 400V rated voltage for AC1: 2106 kW,
- Total power loss for rated current: 1020 W,
- Power loss per pole for rated current: 340 W.