Isolating Load Switch. It is perfectly adapted to meet the current requirements resulting from everyday electrical installation practice.
Current:
- Current carrying capacity of AC21 in category A: 2000 A
- Rated operational current (AC23), category A: 800 A
- Current carrying capacity AC21 category B: 2000 A
- Allowable current load AC22 category A : 800 A
- Allowable current load AC22 category B: 800 A
- Rated operational current (AC23) category B: 800 A
- Short-circuit current with gI fuses -gG: 100 kA
- Rated short-time withstand current Icw: 50 kA
- Rated short-time withstand current 1s: 50 kA
Power :
- Rated power below 660V, 50Hz: 185kW
- Active power below 380/415V, 50Hz: 450kW
- Rated switching power at 400V rated voltage for AC1: 1316 kW
- Total power loss at rated current: 420 W
- Power loss per pole at rated current: 140 W< /li>