MRP-201 residual current protection meter WMPLMRP201

Místní index:
NPP016SONE
Katalogové číslo.:
WMPLMRP201
EAN kód:
5907624021112
Výrobce: SONEL
Maximum operating temperature [°C]: 50
Level of security: IP67
Minimum operating temperature [°C]: -10
Cena:
3 856,05 zł
gross / kusů.
(včetně DPH 23%)
do jednoho týdne
Na zakázku
Množství kusů.
(vícenásobné:
1
)
Přidat do žádosti o cenovou nabídku
Přidat do schránky
Vytisknout

Popis produktu

Specialist MRP-201 device for measuring all types of residual current devices - instantaneous, short-delayed, selective; AC, A and B type. It allows to measure the tripping current, tripping time depending on the residual current strength, protective conductor resistance and touch voltage. Measurements can be performed individually or in series in automatic modes (all preset measurements for a given waveform or for all waveforms), it is also possible to simultaneously measure current and tripping time (with one RCD tripping).

Measurement of all types of residual current protections: AC, A, B.

  • measurement of instantaneous, short-delayed and selective residual current devices with rated residual currents IΔn =10, 30, 100, 300, 500 mA ,
  • measurement of circuit breaker tripping current IA and measurement of circuit breaker tripping time tA at currents 0.5IΔn, 1IΔn, 2IΔn , 5IΔn,
  • simultaneous measurement of tripping current IA and tripping time tAI
  • RE and UB measurement without RCD tripping,
  • AUTO function for RCD measurement.

Measurement of alternating voltage and frequency.
Validation making protective conductor connections.
Memory of measurement results (990 cells, 10,000 entries).
Communication with a computer using the OR-1 radio interface included in the set.
Professional software for reading data and creating protocols .

Electrical safety:

  • type of insulation: double, in accordance with PN-EN 61010 - 1, IEC 61557
  • measurement category: CAT IV 300 V, (III 600 V)
  • housing protection degree: IP67

Other technical data:

  • meter power supply: rechargeable battery pack or alkaline batteries (size AA, 4 pcs.)

Nominal usage conditions:

  • operating temperature: -10...+50°C
  • storage temperature: -20...70°C
  • humidity: 20 ...80%

Technické údaje

  • Maximum operating temperature [°C]
    50
  • Minimum operating temperature [°C]
    -10
  • Level of security
    IP67

Podrobnosti o výrobci

  • Výrobce
    SONEL S.A.
  • Adresa
    58-100 Świdnica Wokulskiego 11 Polska

Soubory ke stažení