WME-6 kit (MPI-502, MIC-2510, CMP-400) WMPLWME6

Index local:
NPP182SONE
Numéro de catalogue:
WMPLWME6
Code EAN:
5907624021228
Producteur: SONEL
Impedance [Ω]: 0.01
Rated voltage [kV]: 2.5
Prix:
9 348,00 zł
gross / pcs.
(y compris la TVA 23%)
En rupture de stock
Ajouter à la demande de devis
Imprimer

Description du produit

A set of meters that allow you to perform all measurements of electrical installations:

  • short-circuit loop impedance with a resolution of 0.01 Ω (also in installations equipped with RCDs),
  • parameters of circuit breakers RCD type AC and A,
  • continuity of protective and equipotential bonding,
  • insulation resistance with voltage up to 2.5 kV (also cable measurements).

The set includes the following devices: MPI-502, MIC-2510 and CMP-400 with accessories.

​MPI-502 multifunctional meter of electrical installation parameters

< p> The device allows you to measure:

  • short-circuit loop impedance;
  • short-circuit loop impedance in circuits with RCDs;
  • < li> all parameters of residual current devices;
  • continuity of protective and equipotential bonding (in accordance with the requirements of the PN-EN61557 standard);
  • mains voltage and frequency.

Measurement of short-circuit loop impedance can be carried out for a wide range of voltages (100...440 V) in L-N, L-L, L-PE circuits. Measurements are made using a method that guarantees high accuracy of the result (measuring range according to PN-EN61557 in the range of 0.13...2000 Ω). The MPI-502 also enables the measurement of short-circuit loop impedance in the L-PE circuit for networks protected by RCDs, which is carried out with a very low current, but in a way that also ensures very high accuracy. Another function of the MPI-502 is the measurement of AC and A type RCDs; regular, selective and short delay. Measurements can also be performed in the Auto mode (several selected RCD measurements without the need for their subsequent triggering, including the measurement of the short-circuit loop). A unique feature is the ability to measure the tripping time and current with only one tripping of the circuit breaker.

The measurement results (990 results of each type) stored in the memory can be sent wirelessly to the computer using the included adapter - OR radio receiver -1 (USB).
A modern housing with a large, legible display offers comfort of use and protects against possible damage.

The MPI-502 is an ideal choice for people who prefer small and handy devices.< /p>

MIC-2510 insulation resistance meter

Insulation resistance measurement:

  • up to 2 TΩ in accordance with IEC 61557-2,
  • selectable measuring voltage 100, 250, 500, 1000, 2500 V or freely adjustable in the range of 50...2500 V with a resolution of 10 V,
  • continuous indication of the measured insulation resistance or leakage current,
  • automatic discharge of the capacitance of the measured object after completing the insulation resistance measurement,
  • acoustic determination of five-second time intervals to facilitate the capture of time characteristics,
  • < li> measured measurement times T1, T2 and T3 for the measurement of one or two absorption coefficients in the range of 1...600 s,
  • automatic measurement of multi-conductor cables possible using an additional AutoISO-2500 adapter,
  • indication of the actual test voltage during the measurement,
  • protection against the measurement of live objects.

Measurement of the continuity of protective and equipotential bonding connections in accordance with PN-EN 61557 - 4 current >200 mA.

Low-voltage measurement of circuit continuity and resistance:

  • measurement of circuit resistance (<999 Ω) current of <15 mA,
  • quick acoustic signaling for a circuit with a resistance lower than 10 Ω,
  • compensation (auto-zeroing) of the resistance of test leads.
< p> Possibilities: Leakage current measurement during insulation resistance measurement. Capacitance measurement during RISO measurement. Continuous measurement of the ambient temperature with the option of saving the result in memory. Measurement of direct and alternating voltages in the range of 0...600 V. Memory of 990 cells (11880 entries) with the possibility of wireless data transfer to a PC using the USB - OR-1 adapter or via a USB cable.

CMP-400 digital clamp meter

The CMP-400 clamp meter is designed for direct measurement of alternating current up to 400 A. The device can also measure direct and alternating voltages up to 600 V with the use of additional test leads. An additional advantage of the meter is the measurement of resistance and continuity of connections with acoustic signaling. It is also possible to measure the temperature using the probe supplied with the meter.

Données techniques

  • Impedance [Ω]
    0.01
  • Rated voltage [kV]
    2.5

Détails du fabricant

  • Producteur
    SONEL S.A.
  • Adresse
    58-100 ŚWIDNICA Armii Krajowej 29
  • Numéro identifiant TVA
    8840033448

Fichiers à télécharger