Product description

Multifunctional meter of electrical installation parameters

With emphasis on insulation resistance measurements

The Sonel MPI-525 multifunctional meter of electrical installation parameters is an innovation in its category. It provides many possibilities to measure the parameters of electrical installations, making it a recommended solution for installers, as well as advanced measuring technicians.

As one of the few meters on the market, Sonel MPI-525 has the ability to measure insulation resistance with a voltage of up to 2500 V. In addition, the device enables automatic measurement of the insulation resistance of 3-, 4- or 5-core wires or cables using the optional AutoISO-2500 adapter.

The MPI-525 meter can be used to precisely measure short-circuit loop impedance (resolution 0.01 Ω) in L-PE circuits in networks with RCDs. Another valuable function of the device is the ability to measure the actual tripping time and tripping current of the RCD with a single tripping of the circuit breaker.

Features

The meter is characterized by extensive possibilitiesin terms of functionality. It combines the measurement capabilities of several devices, while ensuring equally good accuracy. The device can be used to perform all acceptance measurements of electrical installations in accordance with applicable regulations:

  • fault loop impedance (also in circuits with RCDs),
  • parameters of RCDs,
  • insulation resistance,
  • Earth resistance (3-wire method),
  • continuity of protective and equalizing connections,
  • phase sequence test

Additional Features

  • Checking the correct connection of the PE wire using a touch electrode.
  • Measurement of voltage (0...500 V) and mains frequency.
  • Memory 990 results.
  • Wireless data transmission to a computer.

2.5 kV insulation test

A unique feature of the meter is the ability to measure insulation resistance with a voltage of up to 2500 V. Moreover, using the AutoISO-2500 adapter, the user can check the RISO of 3-, 4- and 5-wire.

The instrument has a built-in stopwatch. It has the ability to set three times for conducting and reading measurement results (in the range of 1...600 s). In addition, it automatically calculates two absorption coefficients.

In order to ensure the safety of the user, after the measurement is completed or interrupted, the device automatically discharges the tested object.

Installation security check

With the instrument, you can control domestic and industrial electrical installations in terms of safety. Measurements can be easily automated by:

  • testing of RCDs in Auto mode,
  • using the AutoISO-2500 adapter to test the insulation resistance of 3-, 4- and 5-core wires.

Increased resistance to environmental conditions

The meter will cope well in harsh environmental conditions. Protection against the ingress of dust and water is provided by a unique housing with an IP54 tightness level. It is resistant to mechanical damage, and the special design allows you to easily protect the display by moving the meter cover. In addition to the fact that it protects against damage, it also allows you to conveniently carry and use the device in various positions.

Communications and Software

Through the USB port or using wireless communication, you can transfer the measurement data to a computer. In order to generate a test report in the field of electric shock protection, use the Sonel Electrical Measurements program. Saving the downloaded resources to the simplest formats and printing is provided by Sonel Reader.

 

Measurement functions Measurement range Display range Resolution Accuracy
Fault loop impedance        
ZL-PE, ZL-N, ZL-L short-circuit loop 0.13 Ω…1999.9 Ω according to IEC 61557 0.00 Ω…1999 Ω will give 0.01 Ω ±(5% m.v. + 3 digits)
ZL-PE short-circuit loop in RCD mode from 0.50 Ω…1999 Ω according to IEC 61557 0.00 Ω…1999 Ω will give 0.01 Ω from ±(6% m.v. + 5 digits)
Measurements of RCD Parameters        
RCD tripping test and tripping time measurement tA measuring current 0.5 IΔn, 1 IΔn, 2 IΔn, 5 IΔn        
RCD of general type and short delay 0 ms…300 ms 0 ms…300 ms 1 ms ±(2% m.v. + 2 digits)
Selective RCD 0 ms…500 ms 0 ms…500 ms 1 ms ±(2% m.v. + 2 digits)
Measuring RCD trip current IA measuring current 0.2 IΔn…2.0 IΔn        
for sinusoidal residual current (AC type) 3.0mA…1000mA 3.0mA…1000mA from 0.1mA ±5% IΔn
for 1-way and 1-way differential current with 6 mA dc bias (type A) 3.5mA…700mA 3.5mA…700mA from 0.1mA ±10% IΔn
for DC residual current (type B) 2.0mA…1000mA 2.0mA…1000mA from 0.1mA ±10% IΔn
Ground resistance        
3-wire method from 0.5 Ω…1.99kΩ according to IEC 61557-5 0.00 Ω…1.99kΩ from 0.01 Ω from ±(2% m.v. + 3 digits)
Insulation resistance        
Measuring voltage 50 V 50kΩ…250MΩ according to IEC 61557-2 0 kΩ…250 MΩ from 1kΩ ±(3% m.v. + 8 digits)
Measuring voltage 100V 100kΩ…500MΩ according to IEC 61557-2 0 kΩ…500 MΩ from 1kΩ ±(3% m.v. + 8 digits)
Test voltage 250V 250 kΩ…999 MΩ according to IEC 61557-2 0 kΩ…999 MΩ from 1kΩ ±(3% m.v. + 8 digits)
Measuring voltage 500 V 500kΩ…2.00 GΩ according to IEC 61557-2 0 kΩ…2.00 GΩ from 1kΩ from ±(3% m.v. + 8 digits)
Measuring voltage 1000V 1000kΩ…3.00 GΩ according to IEC 61557-2 0 kΩ…3.00 GΩ from 1kΩ from ±(3% m.v. + 8 digits)
Test voltage 2500V 2.50 MΩ…9.99 GΩ according to IEC 61557-2 0 kΩ…9.99 GΩ from 1kΩ from ±(3% m.v. + 8 digits)
Resistance of protective and equipotential wires        
Continuity measurement of protective and equipotential bonding with ±200 mA 0.12 Ω…400 Ω according to IEC 61557-4 0.00 Ω…400 Ω from 0.01 Ω ±(2% m.v. + 3 digits)
Low current resistance measurement 0.0 Ω…1999 Ω 0.0 Ω…1999 Ω from 0.1 Ω ±(3% m.v. + 3 digits)
Phase sequence indication positive, negative, voltage UL-L: 95 V…500 V (45 Hz…65 Hz)      

 

Adapter for multicore cables

Depending on the measurement object and the adopted standards (each core with each core or a core with other short-circuited and grounded conductors), the measurement of the insulation resistance of wires or multi-core cables requires several connections. In order to shorten the testing time and eliminate inevitable connection errors, Sonel has introduced an adapter that performs switching between individual pairs of wires for the operator.

The AutoISO-2500 adapter is used to measure the insulation resistance of cables and multi-core wires with a measuring voltage of up to 2500 V. The use of the adapter eliminates the possibility of making a mistake, and also significantly reduces the time needed to perform insulation resistance measurements between pairs of wires. For example, for 4-wire cables, the user will perform only one connection operation (that is, he will connect the adapter to the object), while AutoISO-2500 will perform crossover for six consecutive connections.

Technical data

  • Model
    MPI-525 AutoISO-2500

Manufacturer details

  • Manufacturer
    SONEL SPÓŁKA AKCYJNA
  • Address
    58-100 UL. STANISŁAWA WOKULSKIEGO 11
  • Tax identification number
    8840033448
Report an error