Multifunctional meter of electrical installation parameters
Professional measurements made simple
Multifunctional meter of electrical installation parameters Sonel MPI-502 is a compact, equipped with a number of practical functions meter of electrical installation parameters. The MPI-502 model is the successor to the Sonel MIE-500 meter, popular and valued among professionals, which was mainly used for measurements of installations protected by overcurrent and residual current circuit breakers in various types of networks. p>
The Sonel MPI-502 meter is one of the smallest multifunctional measuring instruments on the market. Despite its compact dimensions, the device provides a wide range of functions, and is additionally distinguished by an ergonomic form and a very durable casing. Another advantage of the device worth mentioning is the extremely simple operation, which, in combination with the legible, backlit display, ensures high comfort of use.
The professional Sonel MPI-502 meter can be purchased as a single device, but it is also available in functional, easy-to-carry Sonel WME-5 and Sonel WME-6 sets, which have been created for the needs of installers and measurers. A set with rich equipment is a cost-effective solution aimed at users who perform various types of measurements and want to prepare for work in a comprehensive way.
Features
Additional Features
Simplicity comes at a price
MPI-502 puts emphasis on ergonomics and maximum simplification of the user's work. The selection of functions is carried out using a rotary switch. Additional parameters are set with buttons located on the front of the housing. The settings are remembered by the device even when the battery is completely discharged.
All buttons are backlit, as is the segmented display, making it easy to use in low light. Extensive memory eliminates the need to keep notes during measurements.
Installation security check
With the instrument, you can control domestic and industrial electrical installations in terms of safety. Measurements can be easily automated by:
Increased resistance to environmental conditions
The meter will cope well in harsh environmental conditions. Protection against dust and water ingress is provided by a casing with an IP67 tightness level.
Communications and software
You can transfer measurement data to a computer using Bluetooth wireless communication. In order to generate a test report in the field of electric shock protection, use the Sonel Electrical Measurements program. Saving the downloaded resources to the simplest formats and printing is provided by Sonel Reader.
| Measurement functions | Measurement range | Display range | Resolution | Accuracy |
|---|---|---|---|---|
| Fault loop impedance | ||||
| ZL-PE, ZL-N, ZL-L short-circuit loop | 0.13 Ω…1999 Ω according to IEC 61557 | 0.00 Ω…1999 Ω | from 0.01 Ω | ±(5% m.v. + 3 digits) |
| ZL-PE short-circuit loop in RCD mode | since 0.5 Ω…1999 Ω secondo IEC 61557 | 0.00 Ω…1999 Ω | from 0.01 Ω | from ±(6% m.v. + 5 digits) |
| Measurements of RCD Parameters | ||||
| RCD tripping test and tripping time measurement tA measuring current 0.5 IΔn, 1 IΔn, 2 IΔn, 5 IΔn | ||||
| RCD of general type and short delay | 0 ms…300 ms | 0 ms…300 ms | 1 ms | ±(2% m.v. + 2 digits) |
| Selective RCD | 0 ms…500 ms | 0 ms…500 ms | 1 ms | ±(2% m.v. + 2 digits) |
| Measurement of RCD trip current IA measuring current 0.3 IΔn…2.0 IΔn | ||||
| for sinusoidal residual current (AC type) | 3.0mA…500mA | 3.0mA…500mA | from 0.1mA | ±5% IΔn |
| for 1-way and 1-way differential current with 6 mA dc bias (type A) | 4.0mA…420mA | 4.0mA…420mA | from 0.1mA | ±10% IΔn |
| Resistance of protective and equipotential wires | ||||
| Continuity measurement of protective and equipotential bonding with ±200 mA | 0.12 Ω…400 Ω according to IEC 61557-4 | 0.00 Ω…400 Ω | from 0.01 Ω | ±(2% m.v. + 3 digits) |
| Low current resistance measurement | 0.0 Ω…1999 Ω | 0.0 Ω…1999 Ω | from 0.1 Ω | ±(3% m.v. + 3 digits) |
Program for creating protocols from installation security tests
The latest version of the popular program for creating protocols from electrical measurements. PE6 simplifies the documentation process. It minimizes its time. It automates. All thanks to numerous built-in mechanisms, tools and functions.
Program features:
The program supports the creation of documentation after tests in the field of comprehensive control of measurement points and:
Hardware requirements: