Multifunction meter MPI-530-IT of the latest generation, allowing to perform all measurements in the electrical installation in accordance with the PN-EN 61557 standard:
- short-circuit loop impedance with resolution up to 0.001 Ω – accurate measurement also in circuits with RCDs,
- parameters of RCDs, also in isolated IT networks,
- insulation resistance,
- earthing resistance ,
- continuity of protective and equipotential bonding.
The device has an innovative memory that allows saving tens of thousands of results in the structure of a ready protocol.
Data from memory can be transmitted to a PC via a USB cable or wirelessly via Bluetooth®.
Fault loop impedance measurements:
- measurement of short-circuit loop impedance with a resolution of 0.001 Ω with a current of 23 A (44 A at phase-to-phase voltage) - short-circuit resistor Rzw = 10 Ω,
- measuring voltage range: 95...440 V, frequency 45...65 Hz,
- measurement of short-circuit loop impedance with a resolution of up to 0.01 Ω, in installations protected by RCDs with IΔn ≥ 30 mA without tripping,
- automatic calculation of short-circuit current; distinguishing phase-to-phase voltage and phase-to-phase voltage,
- measurements using UNI-Schuko plug with a button that triggers the measurement (also with L and N wires swapped) or 1.2 m, 5 m, 10 m, 20 m long wires with possible use of 3-phase socket adapters. (AGT),
- selection of installation protections and automatic assessment of the measurement result.
Testing of AC, A, F and B RCDs:
- measurement of ordinary, short-time delay and selective circuit breakers with rated residual currents of 10, 30, 100, 300, 500 and 1000 mA,
- function of automatic measurement of a full set of circuit breaker parameters (after pressing the "START" button once, the meter performs the entire programmed cycle of measurements, including the possibility of measuring the impedance of the L-PE short-circuit loop with a current of 15 mA),
- user-selectable shape of the forced leakage current waveform: sinusoidal (starting from the rising edge or (positive or negative), unidirectional pulsating (positive or negative), unidirectional pulsating with DC bias (positive and negative), constant (positive and negative),
- measurement of IA trigger current with increasing current,
- measurement of tripping time tA at currents ½IΔn, 1IΔn, 2IΔn and 5IΔn ,
- measurement of touch voltage UB and protective conductor resistance RE without tripping the circuit breaker,
- detection of L and N wires inversion in the socket ; does not affect the performance of measurements,
- possibility to measure tripping current IA and real tripping time tAI with one RCD trip,
- measurements for voltage 95...270 V.
< /ul> Insulation resistance measurements:
- measurement voltages: 50 V, 100 V, 250 V, 500 V and 1000 V,
< < /li> - automatic discharge of the capacitance of the measured object after the measurement is completed,
- acoustic determination of five-second time intervals to facilitate the capture of time characteristics during insulation resistance measurement.
Low-voltage measurement of protective and equipotential bonding resistance:
- measurement of protective conductor continuity with current ≥200 mA in two directions,
- low current measurement with acoustic signaling, li>
- auto-calibration of test leads - possibility to use test leads of any length.
Earth resistance measurements:
- technical method measurement
Measurement of soil resistivity using the Wenner method.
Measurement of illuminance.
Quick check of correctness of PE protective conductor connection with using a touch electrode.
Measurement and recording of voltage, frequency, alternating current, cosφ and power (active, reactive, apparent), voltage and current harmonics up to 40, THD coefficients.< /strong>
Checking the motor phase sequence and rotation.
Memory with a tree structure, dynamically managed (max. 10,000 results for each type of measurement) with the possibility of describing measurement points, objects, customer names.
Battery or battery powered (option), built-in quick charger. Possibility of charging from the mains and from the cigarette lighter (12 V).
Electrical safety:
- type of insulation: double, in accordance with to PN-EN 61010-1 and IEC 61557
- measurement category: IV 300 V (III 600 V)
- degree of protection: IP54