The MI 3102 BT model is a multifunctional measuring device that performs all necessary measurements in low-voltage electrical installations in accordance with the PN-EN 61557 standard. This device has an implemented AUTO SEQUENCE mode, which allows you to automate measurements in TN, TT and IT networks (ISFL, IMD). In addition, the MI 3102 BT EurotestXE device allows you to monitor the mains voltage in real mode, check the correctness of the phase sequence, measure the earth resistance, illuminance and current (TRMS value). The meter has implemented overcurrent protection characteristics and an RCD residual current device, which allows for immediate evaluation of the measurement result (Positive/Negative). All results can be easily stored in memory and then copied to a PC using the Metrel Electrical Safety Manager software (included as standard!) for processing and reporting.
Measurement functions
Use features
Application
STANDARDS
Functionality: PN-EN 61557, DIN 5032
Other standards:PN-HD 60364-4-41, PN-EN 61008, PN-EN 61009, BS 7671, AS/NZ 3017, CEI 64.8, HD 384, VDE 413
Electromagnetic compatibility: PN-EN 61326
Safety: PN-EN 61010-1, PN-EN 61010-031, PN-EN 31010-2-030, PN-EN 31010-2-032
CONTINUITY
| Function | Measurement range | Resolution | Accuracy |
| Test current 7 mA 2-wire | 0.00 Ω ... 19.99 Ω 20.0 Ω ... 1999 Ω |
0.1 Ω 1 Ω |
±(5% of reading + 5 digits) |
| Test current 200mA 2-wire | 0.00 Ω ... 19.99 Ω 20.0 Ω ... 99.9 Ω 100.0 Ω ... 1999 Ω |
0.01 Ω 0.1 Ω 1 Ω |
±(3 % of reading + 3 digits) ±(5 % r.v.) ±(5% r.v.) |
INSULATING RESISTANCE
| Function | Measurement range | Resolution | Accuracy |
| Test voltage 50/100/250V | 0.00 MΩ ... 19.99 MΩ 20.0 MΩ ... 99.9 MΩ 100.0 MΩ ... 199.9 MΩ |
0.01 MΩ 0.1 MΩ |
±(5 % of reading + 3 digits) ±(10 % r.v.) ±(20 % r.v.) |
| Test voltage 500/1000V | 0.00 MΩ ... 19.99 MΩ 20.0 MΩ ... 99.9 MΩ 200 MΩ ... 999 MΩ |
0.01 MΩ 0.1 MΩ 1 MΩ |
±(5 % of reading + 3 digits) ±(5 % r.v.) ±(10 % r.v.) |
RCD
| Function | Measurement range | Resolution | Accuracy |
| RCD Uc | 0.00V ... 19.99V 20.0V ... 99.9V |
0.1V | (-0%/±15 %) w.v. ± 10 digits (-0%/±15%) r.d. |
| RCD(t) | 0.00 ms ... 40.0 ms 0.0 V ... max time |
0.1 ms | ±1 ms ±3ms |
| RCD AND Ramp | 0.2xI∆N ... 1.1xI∆N (AC) 0.2xI∆N ... 1.5xI∆N (A), I∆N ≥30mA) 0.2xI∆N ... 2.2xI∆N (A), I∆N 0.2xI∆N ... 2.2xI∆N (B) |
0.05xI∆N | ±0.1xI∆N |
IMPEDANCE
| Function | Measurement range | Resolution | Accuracy |
| Zline L-L, L-N Ipsc | 0.00 Ω ... 9.99 Ω 10.0 Ω ... 99.9 Ω 100 Ω ... 999 Ω 1.00 kΩ ... 9.99 kΩ |
0.01 Ω 0.1 Ω 1 Ω 10 Ω |
“±(5% of reading + 5 digits) ±(10 % r.v.)” |
| Zloop L-PE, Ipfc | 0.00 Ω ... 9.99 Ω 10.0 Ω ... 99.9 Ω 100 Ω ... 999 Ω 1.00 kΩ ... 9.99 kΩ |
0.01 Ω 0.1 Ω 1 Ω 10 Ω |
±(5 % of reading + 5 digits) ±(10 % r.v.) |
VOLTAGE
| Function | Measurement range | Resolution | Accuracy |
| TRMS | 0 … 550V | 1V | ±(2 % of reading + 2 digits) |
| Frequency | 0.00 Hz .. 9.99 Hz 10.0 Hz ... 499.9 Hz |
0.01Hz 0.1Hz |
±(0.2 % of reading + 1 digit) |
CURRENT
| Function | Measurement range | Resolution | Accuracy |
| TRMS, AC with A1018 | 0.0mA ... 99.9mA 100mA ... 999mA 1.00A ... 19.99A |
0.1mA 1mA 0.01A |
±(5 % of reading + 5 digits) ±(3 % of reading + 3 digits) ±(3% r.v.) |
| TRMS, AC with A1019 | 0.0mA ... 99.9mA 100mA ... 999mA 1.00A ... 19.99A |
0.1mA 1mA 0.01A |
pointing ±(5 % r.v.) ±(3% r.v.) |
| TRMS, AC/DC with A1391, range=40A | 0.00A ... 1.99A 2.00 A ... 19.99 A 20.0A ... 39.9A |
0.01A 0.01A 0.1A |
±(3 % of reading + 3 digits) ±(3 % r.v.) ±(3% r.v.) |
| TRMS, AC/DC with A1391, range = 300A | 0.00A ... 19.99A 20.0A ... 39.9A 40.0A ... 299.9A |
0.01A 0.01A 0.1A |
pointing ±(3 % of reading + 5 digits) |
EARTH RESISTANCE
| Function | Measurement range | Resolution | Accuracy |
| 3-wire | 0.00 Ω ... 19.99 Ω 20.0 Ω ... 199.9 Ω 200.0 Ω ... 9999 Ω |
0.01 Ω 0.1 Ω 1 Ω |
±(5% of reading + 5 digits) |
| 2-clamp | 0.00 Ω ... 19.99 Ω 20.0 Ω ... 30.0 Ω 30.1 Ω ... 99.9 Ω |
0.01 Ω 0.1 Ω 0.1 Ω |
±(10 % of reading + 10 digits) ±(20 % r.v.) ±(30 % r.v.) |
| Soil resistivity | 0.0 Ωm … 99.9 Ωm 100 Ωm ... 999 Ωm 1.00kΩm ... 9.99kΩm 10.0kΩm ... 99.9kΩm |
0.1 Ωm 1 Ωm 0.01 kΩm 0.1 kΩm |
±(5 % r.v.) for Re 1 Ω … 1999kΩ ±(10 % r.v.) for Re 2 kΩ … 19.99kΩ ±(20 % r.v.) for Re > 20kΩ |
FIRST FAILURE CURRENT TEST
| Function | Measurement range | Resolution | Accuracy |
| Fault current test 1 | 0.0 mA ... 19.9 mA | 0.1mA | ±(5% of reading + 3 digits) |
IMD TEST
| Function | Measurement range | Resolution | Accuracy |
| Indicative thresholds insulation resistance |
5 … 640kΩ | 5kΩ | Indicative values, up to 128 steps |
LIGHTING INTENSITY
| Function | Measurement range | Resolution | Accuracy |
| Type B | 0.01 lux ... 19.99 lux 20.0 lux ... 199.9 lux 200 lux ... 1999 lux 2.00 klux ... 19.99 klux |
0.01 lux 0.1 lux 1 lux 10 lux |
±(5 % of reading + 2 digits) ±(5% r.v.) |
| Type-C | 0.01 lux ... 19.99 lux 20.0 lux ... 199.9 lux 200 lux ... 1999 lux 2.00 klux ... 19.99 klux |
0.01 lux 0.1 lux 1 lux 10 lux |
±(10 % of reading + 3 digits) ±(10 % r.v.) |
General Data
| Power | 9 VDC (6 x 1.5 V battery or rechargeable AA size) |
| Overvoltage category | 1000VDC CAT II; 600V CAT III; 300V CAT IV |
| Protection class | Double insulation |
| Communication | BT, USB, RS232 |
| Weight | 1.3 kg |
| Dimensions | 230 x 103 x 115mm |