On request
SLS circuit breakers - selective overcurrent circuit breakers
for mounting on busbars:
• for busbars with a distance of 40 mm Cu 5/10x12 mm according to DIN 43870 part 2
• for currents from 10 to 63 A, outputs 1.5 to 16 mm² with screwless terminals
• VDE mark, production control expertise in accordance with reg. VDE No. A639
Tested and certified according to E DIN VDE 0643:2003-09 chapter 5 to 8.18 and DIN EN 60947-1 (VDE 0660 Teil 100):2002-12 EN 60947-1:1999 chapter 8.2.5.2, 8.2.5.3. A1:2000 and A2:2003 DIN VDE 0641-21
• main place of application:
pre-meter protection
• Tripping characteristic Cs -
thermal trigger
1.13 to 1.45 x IN
- electromagnetic trigger
6.5 x 10 IN
• rated voltage 230/400V~
• short-circuit switching capacity 25 kA
• can be closed and locked as standard
• L1, L2, L3 supplied separately
• contact position status indicator
• compliant with EN 60898
| A kind of package | Karton | Pakiet | Paleta |
| Quantity | 1 pcs. | 8 pcs. | 192 pcs. |
| Weight (kg) | 1,323 | 10,974 | 288,376 |
| Width (m) | 0,180 | 0,310 | 0,800 |
| Length (m) | 0,080 | 0,210 | 0,990 |
| Depth (m) | 0,150 | 0,360 | 1,200 |