184143
0
Fuse links, with their advantages (speed of operation, large current range, price), have operational disadvantages that are difficult to accept: manual replacement when tripped, tripping characteristics not adapted to new automatic circuit breakers, impermanence of protective properties due to aging of elements
The selective circuit breaker meets these disadvantages by offering ease of operation of the circuit breaker, high short-circuit resistance (25 kA) and full selectivity for protected standard circuit breakers. For the needs of full integration with the basic protections, special tripping characteristics E and Cs have been developed, which allows for full use of the protection capabilities of the entire system.
SLS circuit breakers - selective overcurrent circuit breakers
for rail mounting TS35:
• SLS circuit breakers can be mounted on a TS35 mounting rail or using an adapter on busbars (spacing
40 mm)
• VDE mark, production control expertise
• tested and certified according to E DIN VDE 0643:2003-09, DIN VDE 0641-21
• main application: pre-meter protection
• in accordance with EN 60898
• tripping characteristics E -
- thermal release
1.05 to 1.20 x IN
electromagnetic release
5 x 6.25 IN
• rated voltage:
230/400V~
• short-circuit breaking capacity
25 kA
• can be closed and locked as standard
• L1, L2, L3 switched separately
• contact position status indicatorów
• cage clamps:
- wire up to 50 mm²
- strand up to 35 mm²
A kind of package | Karton | Pakiet | Paleta | |
Quantity | 1 pcs. | 3 pcs. | 24 pcs. | 576 pcs. |
Weight (kg) | 0,320 | 1,042 | 8,776 | 235,624 |
Width (m) | 0,027 | 0,120 | 0,315 | 0,800 |
Length (m) | 0,110 | 0,084 | 0,214 | 1,006 |
Depth (m) | 0,089 | 0,152 | 0,373 | 1,200 |