MCB Circuit Breaker 6kA 4 Pole 13A Characteristic C MCN413E

local index:
ABC193HAGE
Catalog No:
MCN413E
EAN code:
3250614314117
Manufacturer: HAGER
Characteristic: c
Rated frequency [Hz]: 60
Depth [mm]: 70
Price:
34,61 €
gross / pcs.
(including VAT 23%)
Delivery in 3h
up to 10 weeks (business days)
Pickup in 1h
Quantity pcs.
(multiplicity:
1
)
Add to clipboard
Print

Product description

MCB circuit breaker to protect the electrical installation against the effects of short circuits and overloads. It can also be used as a means of protection against electric shock - automatic shutdown in the event of a short-circuit with negligible impedance between the line conductor and the accessible conductive part or the protective conductor.

Technical data

  • Characteristic
    c
  • Depth [mm]
    70
  • Tightening torque [Nm]
    2.8
  • Rated current [A]
    13
  • Level of security
    IP20
  • power loss [W]
    9.1
  • Width [mm]
    70
  • Height [mm]
    83
  • Mechanical durability (number of cycles)
    20000
  • Rated short-circuit breaking capacity [kA]
    6
  • Rated short-circuit breaking capacity Icn [kA]
    6
  • Max/min value of the AC current of the protection activation
    5/10 In
  • Ultimate short-circuit breaking capacity per pole for 400V [kA]
    3
  • Rated current at 30°C [A]
    13
  • Rated current at 45°C [A]
    12
  • Rated current at 55°C [A]
    11.3
  • Rated current at 65°C [A]
    10.6
  • Operating short-circuit breaking current Ics [kA]
    6
  • Supply voltage type
    AC
  • Rated current correction factor for 3 devices installed side by side
    0.95
  • Number of protected poles
    4
  • Rated frequency [Hz]
    60
  • Number of poles
    4
  • Rated insulation voltage [V]
    500
  • Family
    MCB
  • Power dissipation [W]
    3.5
  • Power loss per pole [W]
    2.3
  • Connection type
    With a screw
  • Electrical endurance (number of cycles)
    4000
  • Operating temperature range [°C]
    from -25 to 60
  • Rated switching voltage [V]
    230/400
  • Number of modules
    4
  • Ultimate short-circuit breaking capacity Icu for 415V [kA]
    10
  • Rated current at 20°C [A]
    13.6
  • Rated current at 40°C [A]
    12.4
  • Rated current at 50°C [A]
    11.7
  • Rated current at 60°C [A]
    11
  • Rated current at 70°C [A]
    10.2
  • storage temperature [°C]
    from -25 to 80
  • Rated current correction factor for 2 devices installed side by side
    1
  • Rated surge voltage [V]
    4000
  • PKWIU
    27.12.22.0

Other technical data

  • Built-in depth
    70 mm
  • Number of poles (total)
    4
  • Rated current
    13 A
  • Rated insulation voltage Ui
    500 V
  • Voltage type
    AC
  • Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V
    10 kA
  • Current limiting class
    3
  • Over voltage category
    3
  • Additional equipment possible
    Yes
  • Degree of protection (IP)
    IP20
  • Connectable conductor cross section multi-wired
    1 ... 25 mm²
  • Release characteristic
    C
  • Number of protected poles
    4
  • Rated voltage
    400 V
  • Rated impulse withstand voltage Uimp
    4 kV
  • Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V
    6 kA
  • Frequency
    50 ... 60 Hz
  • Concurrently switching neutral conductor
    No
  • Pollution degree
    2
  • Width in number of modular spacings
    4
  • Ambient temperature during operating
    -25 ... 70 °C
  • Connectable conductor cross section solid-core
    1 ... 35 mm²

Manufacturer details

Bulk packaging

A kind of package Karton Pakiet Paleta
Quantity 1 pcs. 3 pcs. 36 pcs. 864 pcs.
Weight (kg) 0,392 1,225 15,080 384,920
Width (m) 0,070 0,100 0,310 0,800
Length (m) 0,087 0,085 0,225 1,050
Depth (m) 0,073 0,230 0,365 1,200