MCB Circuit breaker 6kA 1+N 50A characteristic C MCN550E

Lokaler Index:
ABC091HAGE
Katalognummer:
MCN550E
EAN-Code:
3250614314339
Hersteller: HAGER
Characteristic: c
Rated frequency [Hz]: 60
Depth [mm]: 70
Preis:
141,97 zł
gross / stk.
(inklusive MwSt 23%)
Lieferung in 3h
bis zu 10 Wochen (Arbeitstage)
Abholung in 1 Stunde
Menge stk.
(mehrere:
1
)
Zur Angebotsanfrage hinzufügen
Zur Zwischenablage hinzufügen
Drucken

Produktbeschreibung

MCB circuit breaker to protect the electrical installation against the effects of short circuits and overloads. It can also be used as a means of protection against electric shock - automatic shutdown in the event of a short-circuit with negligible impedance between the line conductor and the accessible conductive part or the protective conductor.

Technische Daten

  • Characteristic
    c
  • Depth [mm]
    70
  • Tightening torque [Nm]
    2.8
  • Rated current [A]
    50
  • Level of security
    IP20
  • power loss [W]
    9.2
  • Width [mm]
    35
  • Height [mm]
    83
  • Mechanical durability (number of cycles)
    20000
  • Rated switching voltage [V]
    230
  • Rated short-circuit breaking capacity Icn [kA]
    6
  • Max/min value of the AC current of the protection activation
    5/10 In
  • Ultimate short-circuit breaking capacity per pole for 400V [kA]
    3
  • Rated current at 30°C [A]
    50
  • Rated current at 45°C [A]
    47.3
  • Rated current at 55°C [A]
    44.5
  • Rated current at 65°C [A]
    41.6
  • Operating short-circuit breaking current Ics [kA]
    6
  • Supply voltage type
    AC
  • Rated current correction factor for 3 devices installed side by side
    0.95
  • Number of protected poles
    1
  • Rated frequency [Hz]
    60
  • Number of poles
    2
  • Rated insulation voltage [V]
    500
  • Family
    MCB
  • Power dissipation [W]
    9
  • Power loss per pole [W]
    4.9
  • Connection type
    With a screw
  • Electrical endurance (number of cycles)
    4000
  • Operating temperature range [°C]
    from -25 to 60
  • Short-circuit breaking capacity [kA]
    6
  • Number of modules
    2
  • Ultimate short-circuit breaking capacity Icu for 230V [kA]
    10
  • Rated current at 20°C [A]
    54.5
  • Rated current at 40°C [A]
    48.8
  • Rated current at 50°C [A]
    47
  • Rated current at 60°C [A]
    43
  • Rated current at 70°C [A]
    40.2
  • storage temperature [°C]
    from -25 to 80
  • Rated current correction factor for 2 devices installed side by side
    1
  • Rated surge voltage [V]
    4000
  • PKWIU
    27.12.22.0

Weitere technische Daten

  • Built-in depth
    70 mm
  • Number of poles (total)
    2
  • Rated current
    50 A
  • Rated insulation voltage Ui
    500 V
  • Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V
    6 kA
  • Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V
    10 kA
  • Current limiting class
    3
  • Over voltage category
    3
  • Additional equipment possible
    Yes
  • Degree of protection (IP)
    IP20
  • Connectable conductor cross section multi-wired
    1 ... 25 mm²
  • Release characteristic
    C
  • Number of protected poles
    1
  • Rated voltage
    230 V
  • Rated impulse withstand voltage Uimp
    4 kV
  • Voltage type
    AC
  • Frequency
    50 ... 60 Hz
  • Concurrently switching neutral conductor
    Yes
  • Pollution degree
    2
  • Width in number of modular spacings
    2
  • Ambient temperature during operating
    -25 ... 70 °C
  • Connectable conductor cross section solid-core
    1 ... 35 mm²

Hersteller-Details

Großpackungen

Eine Art Paket Karton Pakiet Paleta Karton Pakiet Paleta
Menge 6 stk. 72 stk. 1728 stk. 6 stk. 72 stk. 1728 stk.
Gewicht (kg) 1,530 18,430 442,360 1,530 18,430 442,360
Breite (m) 0,090 0,310 0,800 0,090 0,310 0,800
Länge (m) 0,080 0,230 1,070 0,080 0,230 1,070
Tiefe (m) 0,220 0,360 1,200 0,220 0,360 1,200
Fehler melden