The characteristics of the WT-gTr fuse-links are matched to the characteristics of the transformer loads and the characteristics of the high-voltage fuses. - The fuse-links are marked according to the transformer power in [kVA] - They enable the use of overload capacity (1.3 x In) - Trip at 1.5 x In occurs within 2 hours - Rated voltage 400, 50Hz - Utilization category: gTr according to VDE 0636/2011 - Short-circuit breaking capacity [kA]: - 100 kA
Technical data
Rated voltage [V]
500
Weight [g]
233
PKWIU
27.12.21.0
Rated current [A]
160
Rated short-circuit capacity [kA]
100 kA
Other technical data
Voltage type
AC
Rated switching capacity
120 kA
Type of fuse status indicator
Combination fuse status indicator
Rated current
160 A
Utilization category
gL/gG (ochrona instalacji elektroenergetycznych przed skutk. zwarć i przeciążeń)