Reaction-to-fire according to EN 13501-6: Smoke production
None
Reaction-to-fire according to EN 13501-6: Acidity
None
Flame retardant
According to IEC/EN 60332-1-2
Low temperature resistant according to EN 60811-504+505+506
No
Wytrzymałość (trwałość) izolacji
No
Permitted cable outer temperature after assembling without vibration
-40 ... +70 °C
Min. permitted bending radius, stationary application/permanent installation
5 mm
Conductor surface
Bare
Conductor category
Class 1 = solid
Specification core insulation
Other
Max. conductor temperature
70 °C
Screen
No
Protective barrier
None
Material outer sheath
None
Reaction-to-fire according to EN 13501-6: Class
Eca
Reaction-to-fire according to EN 13501-6: Flaming droplets/particles
None
Halogen free according to EN 60754-1/2
No
Low smoke (according to EN 61034-2)
No
Oil resistant according to EN IEC 60811-404
No
Outer diameter approx.
3.27 mm
Nominal voltage U0
450 V
Nominal voltage U
750 V
Dane CPR (Construction Products Regulation)
Numer notyfikowanego laboratorium badawczego CE:
nie doty
Wydzielane substancje niebezpieczne:
NPD
Numer referencyjny DoP (DWU)
DOP000035
Oznaczenie produktu
H07V-U 1x2,5 czarny
Reakcja na ogień:
Eca
Zharmonizowana specyfikacja techniczna (norma):
EN 50575:2014, EN50575:2014/A1:2016
Zastosowanie:
Dostawa energii (oraz zastosowania komunikacyjne) w budynkach i innych obiektach budowlanych w celu ograniczenia powstawania i rozprzestrzeniania się ognia i dymu