Descripción del producto

Intended use
The phase loss sensor is designed to protect the motor  power supply from a three-phase network in the event of a power failure in at least one phase or asymmetry of voltage between phases, threatening the destruction of the motor.Action
Power loss in at least one, any phase  or Voltage unbalance [V] between the phases above the activation threshold will cause the motor to be switched off. The switch-off will take place with a delay of 4 seconds, which prevents accidental disconnection of the motor in the event of a momentary voltage drop. Reactivation will occur automatically when  voltage increase by 5V above the operating voltage  (i.e. the value of the voltage hysteresis). With the above anomalies, the engine cannot be started.
 

Datos técnicos

  • Trip voltage unbalance [V]
    55
  • Number of contacts
    0NO 0NC
  • Power [W]
    1.6
  • Shutdown delay [s]
    4
  • connection
    2.5mm screw terminals
  • Dimensions
    2 modules (35mm)
  • Package height [mm]
    150
  • Package weight [kg]
    0.1
  • Voltage hysteresis [V]
    5V~
  • Power control
    3×LED green
  • Installation
    On the TH-35 rail
  • load current [A]
    <10
  • Working temperature [°C]
    -25-50
  • Power
    3×400/230V+N
  • Package width [mm]
    40
  • PKWIU
    27.12.24.0

Otros datos técnicos

  • Type of electric connection
    Screw connection
  • External power supply required
    Yes
  • Supply voltage AC 50 Hz
    150 ... 280 V
  • Phase failure detection
    Yes
  • Function over voltage detection
    No
  • Min. adjustable delay-on energization time
    3.5 s
  • Min. adjustable off-delay time
    1.5 s
  • Number of contacts as normally closed contact
    0
  • Number of contacts as change-over contact
    1
  • Operating voltage AC 50 Hz
    150 ... 280 V
  • With detachable clamps
    No
  • Voltage type (supply voltage)
    AC
  • Phase sequence monitoring
    No
  • Function under voltage detection
    Yes
  • Phase imbalance monitoring
    Yes
  • Max. permitted delay-on energization time
    3.5 s
  • Max. permitted off-delay time
    1.5 s
  • Number of contacts as normally open contact
    0
  • Voltage type (operating voltage)
    AC
  • Rated switch current
    10 A

Detalles del fabricante

  • Fabricante
    F&F Filipowski S.K.
  • Dirección
    95-200 Pabianice Konstantynowska 79/81 Polska

Empaquetado a granel

una especie de paquete Sztuka
Cantidad 1 uds.
Peso (kg) 0,098
Ancho (m) 0,041
Longitud (m) 0,095
Profundidad (m) 0,070