Rated short-circuit capacity:
- 10000 A acc. IEC 61009-1
- 6000 A single pole acc. IEC 61009-1
Types A and AC
Characteristics of overcurrent releases: B and C
Types
- AC: detects alternating leakage currents
- A: detects alternating leakage currents, distorted alternating currents Constant
- Hpi : detects alternating, distorted alternating currents with a dc component
and provides high resistance to unnecessary tripping during transients
Product parameters
Bipolar - 230 V~
Type A
Characteristics of overcurrent releases C
Rated residual current: 30 mA
Rated current: 25 A
Width in 17.5 mm modules: 2