MCB Circuit breaker 10kA, 2P, type B, 10A NBN210

Indice locale:
ABB010HAGE
Numero di catalogo:
NBN210
Codice EAN:
3250614613852
Produttore: HAGER
Rated frequency [Hz]: 50/60
Depth [mm]: 70
Number of poles: 2
Prezzo:
125,99 zł
gross / pezzi
(inclusa IVA 23%)
Consegna in 3 ore
fino a 10 settimane (giorni lavorativi)
Raccolta in 1h
Quantità pezzi
(multiplo:
1
)
Aggiungi alla richiesta di preventivo
Aggiungi agli appunti
Stampa

Descrizione del prodotto

Circuit breakers 0.5 - 63 A. Type B, C and D
Rated short-circuit breaking capacity 10000 A:
• rated ultimate short-circuit breaking capacity (Icu): 15 kA, in accordance with PN-EN 60947-2,
• energy limitation class: 3,
• rated operational voltage:
230/400 V AC - single-pole circuit breaker,
400V AC - omnipolar circuit breaker,
• can be used in DC circuits,
• a wide range of accessories, including insulating barriers between poles,
• possibility of connection using vertical and horizontal comb busbars,
• cage terminals: wire up to 35 mm², stranded wire up to 25 mm²,
• description field with a protective flap,
• top and bottom openable mounting clips,
• degree of protection: IP2X for terminals, IP40 for the device built into the switchgear.

Dati tecnici

  • Rated frequency [Hz]
    50/60
  • Number of poles
    2
  • Rated insulation voltage [V]
    500
  • Power dissipation [W]
    4.13
  • Working temperature [°C]
    -25 to 60
  • Electrical endurance (number of cycles)
    4000
  • Connection type
    With a screw
  • AC rated voltage [V]
    230/400
  • Depth [mm]
    70
  • Tightening torque [Nm]
    2.8
  • Rated current [A]
    10
  • Width [mm]
    35
  • Height [mm]
    83
  • Mechanical durability (number of cycles)
    20000
  • Number of modules
    2
  • PKWIU
    27.12.22.0

Altri dati tecnici

  • Built-in depth
    70 mm
  • Number of poles (total)
    2
  • Rated current
    10 A
  • Rated insulation voltage Ui
    500 V
  • Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V
    10 kA
  • Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V
    10 kA
  • Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V
    15 kA
  • Current limiting class
    3
  • Over voltage category
    3
  • Additional equipment possible
    Yes
  • Degree of protection (IP)
    IP20
  • Connectable conductor cross section multi-wired
    1 ... 25 mm²
  • Release characteristic
    B
  • Number of protected poles
    2
  • Rated voltage
    400 V
  • Rated impulse withstand voltage Uimp
    6 kV
  • Voltage type
    AC
  • Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V
    30 kA
  • Frequency
    50 ... 60 Hz
  • Concurrently switching neutral conductor
    No
  • Pollution degree
    2
  • Width in number of modular spacings
    2
  • Ambient temperature during operating
    -25 ... 70 °C
  • Connectable conductor cross section solid-core
    1 ... 35 mm²

Dettagli del produttore

Imballaggio sfuso

Una specie di pacchetto Karton Pakiet Paleta
Quantità 6 pezzi 72 pezzi 1728 pezzi
Peso (kg) 1,220 14,680 352,510
Larghezza (m) 0,100 0,310 0,800
Lunghezza (m) 0,080 0,230 1,080
Profondità (m) 0,220 0,370 1,200
Segnala un errore