CZF phase decay and unbalance sensor CZF

Indice locale:
APL100FIFQ
Numero di catalogo:
CZF
Codice EAN:
5908312593010
Produttore: F&F
Trip voltage unbalance [V]: 45V~
Depth [mm]: 26
Voltage hysteresis [V]: 5V~
Prezzo:
18,95 €
gross / pezzi
(inclusa IVA 23%)
Consegna in 3 ore
Accessibile 26 pezzi
Raccolta in 1h
Quantità pezzi
(multiplo:
1
)
Aggiungi alla richiesta di preventivo
Aggiungi agli appunti
Stampa

Descrizione del prodotto

Intended use
The phase loss sensor is designed to protect the motor  power supply from a three-phase network in the event of a power failure in at least one phase or voltage asymmetry between the phases, threatening the destruction of the motor.
Action
Power loss in at least one, any phase  or Voltage unbalance [V] between the phases above the activation threshold will cause the motor to be switched off. The switch-off will take place with a delay of 4 seconds, which prevents accidental disconnection of the motor in the event of a momentary voltage drop. Reactivation will occur automatically when  voltage increase by 5V above the operating voltage  (i.e. the value of the voltage hysteresis). With the above anomalies, the engine cannot be started.
 

Dati tecnici

  • Trip voltage unbalance [V]
    45V~
  • Voltage hysteresis [V]
    5V~
  • Power control
    3×LED green
  • Shutdown delay [s]
    4
  • connection
    OMY 4×1mm ; 2×0.75mm, l=0.5m
  • Width [mm]
    67
  • Dimensions
    1 module (18mm)
  • Power
    3×400/230V+N
  • Package width [mm]
    67
  • PKWIU
    27.12.24.0
  • Depth [mm]
    26
  • Number of contacts
    1NO 0NC
  • Power [W]
    1.6
  • load current [A]
    <10
  • Mounting method
    For screws
  • Working temperature [°C]
    -65
  • Height [mm]
    50
  • Package height [mm]
    50
  • Package weight [kg]
    0.1

Altri dati tecnici

  • Type of electric connection
    Soldering flag connection
  • Rated control supply voltage AC 50 Hz
    400 ... 400 V
  • Phase sequence monitoring
    No
  • Function under voltage detection
    No
  • Phase imbalance monitoring
    Yes
  • Min. adjustable off-delay time
    4 s
  • Number of contacts as normally open contact
    1
  • Depth
    65 mm
  • With detachable clamps
    No
  • Voltage type for actuating
    AC
  • Phase failure detection
    Yes
  • Function over voltage detection
    No
  • Voltage measuring range
    140 ... 270 V
  • Max. permitted off-delay time
    4 s
  • Height
    90 mm

Dettagli del produttore

  • Produttore
    F&F Filipowski S.K.
  • Indirizzo
    95-200 Pabianice Konstantynowska 79/81 Polska

Imballaggio sfuso

Una specie di pacchetto Sztuka
Quantità 1 pezzi
Peso (kg) 0,100
Larghezza (m) 0,031
Lunghezza (m) 0,095
Profondità (m) 0,070