Lightning and surge arresters in IP65 housing for protection of the DC side of the inverter with two MPP trackers up to 1000 V, connection via SUNCLIX plug/socket, plug-in varistors with thermal disconnect, between L+, L- and earth/PE.
- Direction of operation: (L+)-PE & (L-)-PE & (L+)-(L-)
- Open circuit voltage UOCSTC 830 V DC (solar generator)
- Rated voltage resistance Uimp 6 kV
- Rated insulation voltage Ui 1000 V DC
- Short-circuit current ISCSTC 25 A DC (per MPP)
- Housing material Glass fiber reinforced polycarbonate
- Cover material Polycarbonate, clear
- Connector material PA
- IEC test classification PV T1
- PV T2
- Rated load current IL 80 A DC
- Residual current IPE ≤ 25 μA
- ≤ 350 μA
- Standby power consumption PC ≤ 25 mVA
- Max. discharge current Imax (8/20) μs 40 kA
- Nominal discharge current W (8/20) μs 15 kA
- Voltage protection level Up (L +) - (L-) ≤ 3.5 kV
- Voltage protection level Up (L + / L-) - PE ≤ 3.5 kV
Residual voltage (L +) - (L -)
- ≤ 3.5kV (input)
- ≤ 2.6kV (at 2kA)
- ≤ 2.9kV (at 5kA)
- ≤ 3.2kV (at 10kA)
- ≤ 3.7kV (at 20kA)
- ≤ 4.1 kV (at 30 kA)
- ≤ 4.6 kV (at 40 kA)
Residual voltage (L + / L-) - PE
< ul>
≤ 3.5kV (at 15kA)≤ 2.6kV (at 2kA)≤ 2.9kV (at 5kA)< /li>≤ 3.2kV (at 10kA)≤ 3.7kV (at 20kA)≤ 4.1kV (at 30kA) ≤ 4.6 kV (at 40 kA)Response time tA ≤ 25 ns
Input: p>
- Connection name DC connection
- Indication of connections IN DC L + / L-
- Connection method PV SUNCLIX connector
- Spring connection< /li>
- Skimmer length 15 mm
- Hose cross section min. 2.5 mm²
- Cable cross section max. 6 mm²
- Cross section 6 mm²
- Outer diameter 5 mm ... 8 mm
- PV1-F type cables
< p>Output:
- Connection name DC output
- Connection name OUT DC L + / L-
- Connection method PV SUNCLIX connector
- Spring connection
- Skimmer length 15 mm
- Hose cross section min. 2.5 mm²
- Cable cross section max. 6 mm²
- Cross section 6 mm²
- Outer diameter 5 mm ... 8 mm
- Cabin type PV1-F
ul>Connection, potential equalization / ground:
- Connection name UT 16-PE
- Connection method Screw terminal blocks
- M5 tap< /li>
- Torque 2.5 Nm ... 3 Nm
- Skimmer length 14 mm
- Hose cross section min. 16 mm²
- Cable cross section max. 25 mm²
- Direct conductor cross-section min. 16 mm²
- Cable cross-section solid max. 25 mm²
- Cable cross-section AWG min. 5
- Wire gauge AWG max. 4
Remote indicator pin
- PDT switching function, 1-pos.
- Connection method MC 1.5 / 3
- M2 tap
- Tightening torque 0.25 Nm, 2 lbf-in. ... 4 lbf-in.
- Skimmer length 7 mm
- Hose cross-section min. 0.14 mm²
- Cable cross section max. 1.5 mm²
- Direct conductor cross-section min. 0.14 mm²
- Cable cross-section solid max. 1.5 mm²
- Cable cross-section AWG min. 30
- Wire gauge AWG max. 14
- Cable size AWG 30 ... 14 (UL)
- Maximum operating voltage Umax. AC 250 V AC
- Maximum operating voltage Umax DC 30 V DC
- Max. operating current Imax 1.5 A AC (250 V AC)
- 1.5 A DC (30 V DC)
Standards / Regulations:
< ul>- IEC 61439-2 2011
- EN 61439-2 2011
- EN 50539-11 Surge Protection